Note: Probes not includes, sold separately
This thermocouple-to-CAN module produces temperature data from 4 thermocouple sensors and outputs it via CAN bus. The module is 100% standalone - no PC required.
The module supports all thermocouple types (B, E, J, K, N, R, S, T) and can be daisy-chained for 8, 12, 16, ... channels.
You can integrate the module with any CAN bus system - e.g. to provide temperature data for your ECUs or existing CAN hardware.
As an example, you can use the module as an add-on for the CANedge - ideal for e.g. engine dynos, EGT analysis, HVAC monitoring and other temperature telematics use cases.
Add temperature sensor data via 4 thermocouples to your CAN bus - e.g. for use by ECUs or CAN hardware.:
- Compatible with any high speed CAN bus (2.0A, 2.0B)
- Fully configure CAN IDs, bit rate and message frequency
- Daisy-chain multiple modules for 8, 12, 16, ... channels
- Power at 5-26 V DC via standard DB9 adapter cables
- Optionally record the data via any CAN interface/logger/...
- Example: Use as add-on for the CANedge (power via 2nd port)
- DBC file included for easy decoding to human-readable form
- White label e.g. for inclusion in your production
Features:
- Plug and Play: Standalone - no PC required. Integrate with any CAN bus to add temperature data. DBC included
- Compact: Only 7 x 2 x 5 CM. 90G. Alu enclosure. 3 LEDs. 5-26 V DC via DB9. USB for config/firmware
- Thermocouples: Output data from 4 thermocouple sensors at 5 Hz in one CAN frame
- Precise: High accuracy. Cold-junction compensation. Line frequency filtering. Fault detection
- Thermocouples: Independently configure each thermocouple channel type (B, E, J, K, N, R, S, T)
- Configurable: Configure CAN IDs, bit rate, message frequencies and more via JSON config and GUI
Specifications
Sensor (Temperature):
- Channels: Supports up to 4 thermocouple sensors/channels (plus ambient temperature via cold-junction)
- Module: Professional-grade MAX31856MUD+ precision thermocouple converter
- Temperature Range: Supports a range of -210 C to +1800 C (depending on thermocouple type)
- Formatting: The module conveniently outputs degrees Celsius via automated edge linearization
- Accuracy: Lab-grade thermocouple voltage measurement accuracy with cold junction compensation
- Resolution: Thermocouple temperature measurements are output on CAN at a 1 degC resolution
- Protection: Thermocouple inputs are protected against overvoltage conditions up to 45V
- Types: Supports thermocouple types B, E, J, K, N, R, S, T (via configuration)
- Filtering Line frequency: filtering of 50Hz and 60Hz (via configuration)
- Fault Detection: Thermocouple fault detection (open thermocouples, over- and under temperature) is communicated via CAN
- Cold Junction: +/- 0.7 C (max, -20 C to +85 C) cold-junction accuracy
Data Parameters:
The module communicates temperatures and fault statuses (for a full list, see the Docs or DBC file)
- Thermocouple temperatures: The degree celsius (degC) temperature of each thermocouple probe [5 Hz]
- Ambient temperature: The ambient temperature measured via internal cold-junction [5 Hz]
- Faults: Status of each thermocouple sensor [5 Hz]
CAN Bus:
- Channels: 1x CAN channel
- Modes: The device can either broadcast the data onto the CAN bus - or provide it on-request
- Standard ISO 11898: Compliant with CAN (between 5K and 1 Mbit/s baud rates)
- Identifiers: Compliant with CAN specifications 2.0A (11-Bit ID) and 2.0B (29-Bit ID)
- Termination: Termination can be toggled via switch below DB9 connector
- Retransmission: Retransmission of frames that have lost arbitration or been disturbed by errors
Configuration:
- Bit Rate: Select between standard bit rates (5K to 1M) or use custom bit-timing
- Enable/Disable: Individually enable/disable the CAN message
Identifier Customization Individually configure the CAN ID (11-bit or 29-bit)
- Push/Poll Mode: Individually configure 'trigger' modes for the CAN messages (push or poll)
- Frequency: Individually configure prescaling of the CAN message frequencies to lower rates
- Thermocouple Type: Specify the thermocouple type for each channel (e.g. Type K, Type J, ...)
- Line Noise Filtering: Select rejection of 50 Hz (EU) and its harmonics or 60 Hz (USA) and its harmonics
Electrical:
- Input Supply: +5V to +26V DC via the DB9 connector (power via pin 1 or pin 9)
- Power Consumption: Extremely low (<1W) - no risk of battery drainage
- Protection: Reverse voltage protection on CAN-bus supply
Mechanical:
- Enclosure & Weight: Compact aluminum enclosure: 52.5 x 70.0 x 24.5 mm (L x W x H) excl. antenna, 90 grams
- Connector: 1x Standard D-sub 9 (DB9) connector
- Pin-Out See the product manual for the DB9 connector pin-outs
- USB: Standard mini USB connector for configuration and firmware updates (USB adapter cable not included)
- LEDs: Module status via 3 external LEDs: Power, CAN bus, Memory
- Temperature Operating temperature (CANmod.temp module): -25degC to +70degC
- IP Rating: IP Rating 40
- Mounting: Module can be mounted via e.g. rugged double-sided tape, zip-ties or a mounting bracket
General:
- Functionality: The device supports 4x thermocouples for outputting temperature sensor data via CAN bus
- Included: CANmod.temp module, USB dust cover (thermocouple sensors and mini USB adapter not included)
- Firmware: Supports free firmware updates via USB for adding features
- Configuration: Configuration files based on the popular open source JSON schema concept (similar to the CANedge)
- Software: Free open source editor tool for easy device configuration (offline/online version available)
- Safety: CE, FCC, IC and RoHS certified (see the Docs for certificates)
- Warranty: 1-year warranty